Abstract
This study addresses heat transfer performance of laminar non-Newtonian fluid flow in various configurations of coiled square tubes e.g., in-plane spiral ducts, helical spiral ducts and conical spiral ducts. The non-Newtonian fluid considered in this study is the aqueous solution of carboxymethyl cellulose (CMC) which is modeled as power-law fluid. Effects of tube geometries, power-law index (concentration of CMC) and other parameters are quantified and discussed to analyze flow behavior and heat transfer performance. Results are compared with those for a straight square tube of the same length as that used to form the coils. A Figure of Merit is defined to compare the heat transfer performance of different geometries with respect to the pumping power. The results suggest that CMC solution yields better heat transfer performance of about twice than that of water at Re~1000. Among all considered designs, helical coil gives the best heat transfer performance; however, when the pumping power is considered, in-plane coil design performs the best in term of Figure of Merit.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Communications in Heat and Mass Transfer
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.