Abstract

This study represents experimental techniques for testing the high-voltage polluted insulators under conditions simulating the natural environment. International Electrotechnical Commission (IEC) fog method is used for testing the insulators of type π-ϕ-E4.5, but it does not simulate the desert pollution environments. For that reason, other two suggested techniques are added to explain the performance of the polluted insulators under dew and under simultaneous fog and dew, respectively. The leakage current bursts are recorded in each test type. Also the effect of the wetting method of the insulators under testing on the flashover voltage is investigated. The results of the three types of tests are compared with each other, under different surface layer conductivities. It is concluded that the analysis of leakage current bursts can be used to monitor the severity of pollution on the electrical network.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.