Abstract

Multiple stroke lightning ground flashes can impose surges of exceptional severity on the arresters used to protect exposed distribution system equipment. This paper reports laboratory and analytical studies of the effects of representative multiple impulse currents on zinc-oxide surge arresters of distribution class. The results indicate that sextuple 8/20 /spl mu/s currents can cause damage to arresters not evident with standard lightning current tests and so are worthy of inclusion in testing Standards. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.