Abstract
Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application environment and topological structure and operating principles of hybrid circuit breakers, and key stress parameters in transient state process of two time dimensions are extracted. The established digital simulation circuit for PSCAD/EMTDC device-level operation of the circuit breaker has verified the stress properties of millisecond level breaking process and microsecond level commutation process. Then, equivalent test method, circuits and parameters based on LC power supply are proposed on the basis of stress extraction. Finally, the results of implemented breaking tests for complete 200kV circuit breaker, 100kV and 50kV circuit breaker units, as well as single power electronic module have verified the accuracy of the simulation circuit and mathematical analysis. The result of this paper can be a guide to electrical structure and test system design of hybrid HVDC circuit breaker.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.