Abstract

An incipient and self-clearing arcing fault can be utilised as a precursor of an imminent permanent failure for monitoring of underground cables. Due to very short duration of the incipient faults, generally they cannot be detected by conventional protection relays. This study presents a new method for detection of incipient cable failures by using measured current and voltage at one end of the cable. The incipient faults are detected using an innovation signal calculated from the measured fault current via a Kalman filter. Upon change detection by the innovation signal, the change is checked for discriminating possible incipient fault from other similar conditions. The proposed method is evaluated using several simulations and field data collected from a real network. The results confirm that the method can achieve high accuracy and speed for detection of cables incipient faults.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.