Abstract

The substation is one of the components in the electric power distribution system which plays a very important role because it is the connection between electricity services to customers. In the electric power distribution system, there are disturbances that often occur, one of which is a short circuit. For that, the way to overcome this is using the Distance Relay protection system, OCR / GFR and DEF. The purpose of writing this research is to determine the value of setting relay distance, setting Over Current Rele and Directional Earth Fault relay in order to secure the 70 kV transmission network connected to GI Banaran, which is then simulated using DigSILENT 15.1 software on the Pare line by calculating symmetrical and asymmetrical disturbances. including 3-phase disturbance on February 1, 2018. The simulation results show that the 3-phase disturbance occurs at Zone 1 relay distance of the Banaran Bay Pare substation with a trip time of 0.02 seconds with a fault impedance of 0.083 ohms below the relay impedance value of 0.887 ohms. The coordination between the distance relay on the side of the Banaran Bay Pare substation has worked well because there is no error reading the relay when it will cut off the disturbance.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call