Abstract
High-voltage and high-power voltage source converters (VSCs) are usually operated at low switching frequencies to minimise the switching losses. This study presents a new control method suitable for low switching frequencies. It consists of two stages. In the first stage, a simple proportional controller is used to suppress any overvoltage or overcurrent during the transients. Then, after the control variables have settled to steady-state values, the iterative controller is activated to finely adjust the modulation index and firing angle of the converter to fulfil the control objectives. To justify the proposed control method, various control objectives are realised in a 10 MVA VSC system, and the results are validated by PSCAD/EMTDC and hardware-in-the-loop simulation. The results show that state variables converge within a few iterative steps, and the transient response is sufficiently fast. The proposed method is shown to perform better than the conventional PI control for eliminating the power imbalance and DC second harmonics due to the imbalance at the grid voltage.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.