Abstract

This paper presents an agent-based protection scheme for distribution networks with distributed generators. The distribution network is divided into several network segments. The relay agents, which are located at the boundaries of these segments, can determine the direction of fault currents using the transients generated by the fault. Fault directions determined by the relay agents located at different points of the network are combined to determine the faulted segment. A fault direction identification technique, which uses the wavelet coefficient of the measured line currents, was developed for relay agents. The performance of the proposed protection scheme is investigated through simulation of a benchmark medium-voltage distribution system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.