Abstract

Natural draft dry cooling tower (NDDCT), with little water usage, is a primary choice for power plants in dried regions. However, the increased ambient temperature during summer days decreases the cooling performance of NDDCT. Inlet air pre-cooling is used to alleviate the tower deterioration by making use of water evaporation to remove excess heat from inlet air. To achieve the maximal cooling effect, the injection heights, radial distances and injection directions of employed nozzle LNN1.5 were studied based on the CFD results. The study shows that lower nozzle placement can cool the central part of the radiator while the higher one cools the middle part. Additionally, the increasing extended length can boost the evaporation process of generated spray. Moreover, the upward and co-flow injections have poorer performance than the downward and counter-flow injections. Furthermore, an introduction of wall cover changes the flow field and drives the pre-cooled air flow through the edge of radiator. Since the wall cover reduces the blockage caused by the near-wall vortex the resultant low-temperature region move outwardly.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.