Abstract

The performance of a forced draft wet cooling tower was investigated experimentally and the calculation was performed by applying second law of thermodynamics (exergy analysis). The mathematical model was developed by using engineering equation solver (EES) software. The results show that the chemical exergy of air increases from the bottom to the top of the cooling tower, the thermal exergy of air decreases from bottom to the top of the cooling, the exergy of water decreases from top to the bottom of the cooling tower. The exergy destruction decreases from bottom to the top of the cooling tower, and the exergy efficiency decreases from top to the bottom of the cooling. The exergy destruction tends to increase as the inlet wet bulb temperature increases while the exergy efficiency decreases. As water-air flow rate ratio increases the exergy destruction increases while the exergy efficiency decreases. The results show that there is an inverse proportional be-tween exergy destruction and exergy efficiency.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.