Abstract
Transformer oil serves as the main dielectric and interacts with solid insulation, encounters the environment, and conveys a lot of information. However, undesirable contamination of transformer oil like water or moisture in the transformer oil will reduce the transformer's effectiveness. This study is the first investigation of the potential of using the thermoelectric effect for transformer oil condition testing towards high voltage insulator oil condition detection. This study has found that the used oil sample with various percentages of water content produced a different Seebeck coefficient which shows the potential of using the thermoelectric effect as a simple, cheap, and versatile method to test industrial oil insulator conditions. The results of the Seebeck coefficient for each condition are 0.0003 mV/K (original), 0.0107 mV/K (4 % of water added), and 0.0131 mV/K (40 % of water added), respectively. The industrial oil shows different Seebeck magnitude between oil before and after thermal aging which show a significant decrease of Seebeck magnitude of the industrial oil insulator with an increase of thermal ageing.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.