Abstract

In order to evaluate the performance of a hybrid compression / ejection refrigeration system using solar energy at low or medium temperature, a simulation model of its behavior based on those of its various components has been developed. It includes in particular for the ejector, a 1-D model of the "constant section mixing" type developed in optimal transition regime. The refrigerants tested are steam for the ejector loop and the R1234yf (replacing the R134a) for the mechanical compression loop. The behavior of the H2O vapor flowing in the ejector is considered that of the perfect gas. The properties of refrigerants are calculated using REFPROP® software, everywhere else. For a cooling capacity of 10 kW and air conditioning operating conditions, the model allows to determine the main parameters of the ejector and its entrainment ratio, the thermal and mechanical COP of the whole refrigeration system as well as the necessary surface of the solar collector. Furthermore, the influence of the temperature of the boiler, the condenser, the intercooler as well as that of the evaporator on the mechanical COP of the hybrid system and the solar collection surface in particular, were examined. The results highlight that the solar refrigeration system with hybrid cycle compression/ejection using the refrigerants H2O/R1234yf allows an increase of the mechanical COP higher than 50% compared to that of the conventional refrigeration system and thus constitutes an acceptable ecologically system that can compete with the latter.