Abstract

In this experiment, the switchable evaporation and condensation horizontal single-tube heat exchange experiment platform is designed. And the equipment selection and construction of the experiment platform is completed through the design calculation. The experimental results show that the thermal balance error of the test section of the experiment platform is less than 15%, especially the condensation and evaporation experiment of R22 in 12.7 mm copper tube, and the evaporation experiment of R410A in 9.52 mm copper tube, the thermal balance error of the experiment is less than 5%. The experiment platform can realize heat exchange experiments with different refrigerants, and the test section of the experiment platform can be standardized replacement of tube types according to research needs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.