As a result of COVID-19, many office buildings around the world have downsized their employees, but the comfort parameters in the building had to be kept. The facilities operation rearranged the workstations to keep physical distance and placed plexiglass sheets on the desks for physical protection. A series of measurements have been carried out with workstation set-ups to examine the fresh air rate in the occupied zone. The effect of plexiglass sheets placed on the desks was also examined to see how it changes the airflow pattern in the occupied zone. As the sheets act as a barrier, the primary air does not reach the occupied zone, therefore, the fresh air rate is less. To modify the properties of the ceiling diffusers a new air-ventilation service element was developed. This attachment allows modifying the properties of the ceiling diffusers. Simulations were made at the relevant zones to validate the measurements. Based on design software, the fresh air ratio for a standard ceiling swirl diffuser is 2.46 v% (volume percentage). A numerical model was used to show the fresh air ratio with the system elements for the two different table arrangements, which were 18.3 v% and 21.4 v%, respectively.