Abstract

In the measurement of the transient recovery voltage (TRV) for short line fault (SLF) artificial line, distinctive TRV waveforms were measured. In the measured waveforms, a center of the TRV voltage oscillation was not constant. Due to the fact, the amplitude factor of the measured TRV was very low. When the SLF artificial line components are composed by linear elements, the center of the TRV oscillation must be constant. And the amplitude of the TRV will be large. This distinctive TRV waveform was generated by the frequency dependence of the air core main reactor for the SLF artificial line. It is shown that the inductance of the main reactor becomes small at high frequency like TRV frequency by skin effect.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.