Abstract

This paper examines a 368 m deep geothermal probe for heating an existing building. The geothermal probe based on the thermosyphon principle works with CO2. The working fluid evaporates and condenses in the probe so that no pump is required for transportation. The geothermal probe has an output of up to 22 kW at an underground temperature of up to 18°C. The demand-controlled use of the geothermal probe was investigated and the installed heat pump was optimized for its use. The average COP of the last heating season was between 2,3 and 4,6. For the second heating season the temperature of the soil around the probe is also measured via a distributed temperature sensing system, that covers the whole depth of the probe. It has been shown that the ground temperature only cools down to a certain point and does not fall below this point after a short regeneration period. It was shown that the heat pump with geothermal probe operates at constant temperatures at the evaporator compared to air heat pumps, even at cold outside temperatures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.