Abstract

The aging of epoxy electrical insulation by unipolar, repetitive voltage surges has been investigated to determine whether such surges can precipitate premature failure of high-voltage motor windings and gas insulated switchgear spacers. A full factorial statistical test was devised and performed on 180 pure epoxy insulation specimens to examine the effect of voltage magnitude, polarity, and surge repetition rate on the life of unfilled epoxy specimens containing a needle-plane electrode geometry. All factors and interactions were determined to have a significant effect on the life, and life prediction equations were estimated. Increasing the voltage magnitude or repetition rate, decreased or increased the life, respectively. Aging was found to occur at as low a stress as 2 MV/cm. Gradual aging of the epoxy does occur under repetitive voltage surges. Based on a realistic number of surges with typical voltage amplitudes which can normally occur from vacuum switchgear during service, gradual deterioration of the epoxy turn insulation in motor stator windings is possible in some situations. Situations where surge aging may occur are identified. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.