Abstract

In HVDC transmission lines, a special phenomenon, so-called single unit flashover, is observed under some special conditions. Only one or two insulator units repeat flashovers, not resulting in an overall flashover along the string. However, higher magnitudes of audible noise, radio and television interferences may give a serious problem. Based on an investigation on /spl plusmn/500 kV full scale insulator strings, the higher occurrence probability of single unit flashovers under cold-wet-switch-on conditions was clarified compared with normal continuous operating voltage conditions. The effectiveness of the authors' newly proposed countermeasures to prevent single unit flashovers was demonstrated by experiments in laboratory and in the field.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.