Abstract

The positive feedback-based anti-islanding scheme has become a common anti-islanding protection technique for inverter-based distributed generators (DGs). This paper investigates the scheme's impact on the small-signal stability of multiple inverter-based DGs installed in power distribution systems during grid-connected operation. The interactions among multiple-DGs due to the anti-islanding scheme are also addressed. An index is proposed to quantify the destabilizing effect of the aggregated positive feedback activities of multiple DGs. This paper further introduces a DG power transfer limit versus islanding detection time curve to reveal the conflicting requirements of anti-islanding protection speed and the maximum power transfer of multi-DG systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.