Abstract

The performance of ceiling-mounted personalized ventilators (PV) in reducing particle migration between office stations was assessed. The PV nozzles were integrated with peripheral diffusers that were able to form a canopy of conditioned air around the occupant. A numerical CFD model was developed to simulate the flow, temperature and particle concentration fields. Validation against experimental measurements and published experimental data was performed. The canopy was effective in reducing the migration of particles from the macroclimate to the microclimate region and low intake fractions of 1.90 × 10−4 and 5.9 × 10−4 were achieved for particle sizes of 1 μm and 0.01 μm, respectively. The PV jet was capable of maintaining an intake fraction of 3.6 × 10−4 for fine particle sizes (1 μm) and 2.95 × 10−4 for ultrafine particles (0.01 μm) when the particle-emitting source is in the proximity of the occupant. However, in spite of the good inhaled air quality achieved by the PV nozzle, the particle deposition rate on solid surfaces that are easily reached by the occupant is high when the source is placed in the microclimate.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.