The article describes design of a pile with new rotary anchors for foundations of buildings operating on variable loads or on heaving soils. The results of plate load tests on piles’ pressing in with one- and two anchor levels are presented. Based on calculations on bearing capacity of piles of proposed design, the adequacy of data on determination of its bearing capacity obtained by experimental method is calculated. Bearing capacity of anchor piles for pulling out is determined by calculations. Anchors located at one level at the height of pile increase its bearing capacity for pressing in by 20%, and increase it for pulling out by 94%. Anchors located at two levels at the height of pile increase bearing capacity of pile for pressing in by 60%, and increase bearing capacity for pulling out by three times. A decrease in the settlement of pile of proposed design is determined by the results of plate load tests on pressing in and it amounts to 85% for a pile with one-level anchors and to 94% for a pile with two-level anchors.