Abstract
Direct lightning strikes to reinforced concrete buildings cause telecommunication equipment to malfunction. The lightning surge currents induced in the building should be investigated to develop the countermeasure method against these strikes. A telecommunication building was modeled by a wire-frame model which presents the beams and pillars of a building. The element of each wire-frame was calculated based on the electromagnetic theory. The induced lightning surge was calculated from the observed waveform of lightning current by using SPICE and FFT. The calculated waveforms at the pillars were compared with observed values. The result showed that a similar waveform could be obtained by the calculation. The calculated deviation of the peak values at pillars almost agreed with the observed value. The results indicate that the model can be used to estimate the tendencies of the lightning surge distribution in reinforced concrete buildings. The lightning surge distribution was calculated by this model. The results showed that the range of value among pillars decreased for the lower floors.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.