Abstract
In this paper, clearing of DC faults in a hybrid multi-terminal HVDC transmission system consisting of line commutated converters (LCCs) and voltage source converters (VSCs) implemented using half-bridge modular multilevel converter (MMC) technology is investigated. While the hybrid HVDC system has several possible configurations, this paper focuses on two of them: 1) a half-bridge MMC-HVDC link piggy-backing on the transmission line of a LCC-HVDC link and 2) LCC-HVDC link tapped by half-bridge MMC inverters. The proposed dc fault recovery strategy employs a high rating series diode valve placed at each VSC inverter pole to block fault currents; AC circuit breakers to isolate the faulty VSC rectifier pole; and force retardation applied at LCC rectifier to extinguish the arc. Detailed simulations demonstrate fast fault recovery performance with the proposed fault recovery procedure. In the case where a single transmission line is shared by the LCC and VSC links, the VSC rectifier is subjected to considerably high current for a period of few hundreds of milliseconds and the ac side voltage dips momentarily. During a single pole fault, interrupting power flow on the healthy pole of VSC rectifier may be necessary to maintain smooth operation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.