Abstract
Overhead Transmission Lines (OTLs) are used in Power Systems to carry High Voltage between substations, usually over long distances. Faults in OTLs are bound to happen and thus locating and coping with them is an important aspect of OTL’s operation and maintenance. These faults may be of temporary or permanent nature, with certain types of faults progressing over time from the first category to the second. Local weather may also have a direct effect on the occurrence of faults resulting to puzzling events. A special category, often complex in nature, is insulator faults. Insulators are used in OTLs to support phase conductors while not allowing current to flow through the tower’s body to the ground. Traditional ceramic insulators used materials such as porcelain and glass as insulation, but in the last decades composite insulators with two insulating parts (a glass core/rod and a rubber housing), have also known great use mainly due to their low weight and their capability to withstand pollution. However, they are subjected to certain faults unique to them, such as flashunders. Flashunder is a term commonly used lately to describe faults that are related to the rod/housing interface of composite insulators. Such faults are rather difficult to locate as the electrical discharge does not create an easily visible trace (as in the case of flashovers) or a permanent mechanical fault (as in the case of brittle fractures). Such a fault occurred for the first time in the Transmission System of Crete in 2019 and this paper follows and discusses the incident and the experience gained.
Highlights
Overhead Transmission Lines (OTLs) are major components of power systems, used in the Power Transmission part of the system to connect High Voltage Substations, usually over long distances
A transient line fault is by definition a fault cleared after a small interruption of power and it is the result of factors that are either temporary in nature or are removed due to the stress induced by the power arc [2,3,4]
This paper focuses on a flashunder fault experienced earlier this year in the transmission system of Crete
Summary
Abstract—Overhead Transmission Lines (OTLs) are used in Power Systems to carry High Voltage between substations, usually over long distances. Faults in OTLs are bound to happen and locating and coping with them is an important aspect of OTL’s operation and maintenance These faults may be of temporary or permanent nature, with certain types of faults progressing over time from the first category to the second. Flashunder is a term commonly used lately to describe faults that are related to the rod/housing interface of composite insulators Such faults are rather difficult to locate as the electrical discharge does not create an visible trace (as in the case of flashovers) or a permanent mechanical fault (as in the case of brittle fractures).
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Engineering, Technology & Applied Science Research
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.