Abstract

This is the first research paper on data center from Finland. The objectives of this study are to evaluate air management and energy performance of cooling system and investigate the possibilities of energy saving and reuse in the data center. Field measurements, particularly for long term's IT and facility powers, were conducted. Different performance metrics for the cooling system and power consumption were examined and analysed. Key problem areas and energy saving opportunities were identified. The electrical end use breakdown was estimated. Results show that IT equipment intake conditions were within the recommended or allowable ranges from ASHRAE. The Power Usage Effectiveness (PUE) value for a typical year was about 1.33. Noticeable recirculation of hot air was not observed, but extreme bypass air was found. The air change rate was set much bigger than the recommended ASHRAE's value. There was no heat recovery system. The air management and heat recovery issues therefore need to be addressed. Fan speeds (Computer Room Air-Conditioning Unit) should be reduced and the ventilation rate should be minimized. Further, a simulated heat recovery system was presented demonstrating that the data center could potentially provide yearly space and hot water heating for 30,916 m 2 non-domestic building.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call