Abstract

1. The device for cooling coarse aggregate in hoppers, designed by the Leningrad branch of Orgenergostroi, cools gravel of all fractions to an average temperature of 4–5°C at a temperature of the cooling air of −3°C. At a temperature of the cooling air from −6 to −8°C, the gravel is cooled to 0 to −2°C. 2. The degree of cooling of the material is easily regulated by changing the rate of air flow. The gravel is cooled uniformly, and freezing together of the pure material is not observed during continuous plant operation. To prevent freezing then the plant is shut down for more than 20–30 min, and the delivery of cooling air must be discontinued. 3. Cooling of sand was ineffective for a number of reasons, the main ones being the large aerodynamic resistance and improper design of the hoppers, which determined the character of sand discharge. 4. To calculate the heat-transfer coefficient when designing such devices, it is recommended that B. I. Kitaev’s formula be used with the introduction of our correction factors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.