Abstract

A pilot-scale test rig was designed and constructed to simulate intrusion behavior associated with hydraulic transients initiated by sudden events such as rapid valve closure or uncontrolled change in on/off pump status (“pump trip”) in a water distribution system. After establishing steady state flow conditions, intrusion volumes were determined for 3.2 (1/8-in.) and 6.4 mm (1/4-in.) diam orifices overlaid with a column of water that provided 91 mm (3 ft) of external head. Average intrusion volumes associated with hydraulic transient events were determined by mass balance calculations using cesium as the tracer chemical. Average intrusion volumes were 11.4 and 71.2 mL for the two diameters, respectively. Given similar conditions in a water distribution system (i.e., an available pathway and favorable pressures), pathogens in the soil and water surrounding a water main potentially can intrude into the pipe during short-term pressure transient events.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.