The proper modeling of the transient thermal behavior of mutual heating effects between underground power cables is very important for the rating of transmission and distribution cables. The IEC standards proposed an accurate model based on exponential integrals that it can be difficult to implement in basic electrical software. The model is not consistent with the layered modeling of the cable thermal resistances. In this paper, a simple and easy-to-use alternative model is presented. It consists of injecting the correct current at the right position of the RC circuit representing the soil. The new model can accurately reproduce the full physics of the transient phenomenon and is consistent with the modeling of the cable used in the IEC standards themselves. The new model is tested and validated against numerous finite-element simulations for realistic cable installations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.