Abstract

By using a 275kV, 150MVA reactor, interrupting tests, were conducted on an opening resistor-fitted air-blast circuit breaker, a two-pressure SF6 gas-blast circuit breaker, and a puffer-type. SF6 gas circuit breaker. Maximum overvoltages generated on the reactor were 1.95 PU with the puffer-type SF6 gas circuit breaker, 2.27 PU with the two-pressure SF6 gas-blast circuit breaker, and 1.71 PU with the opening resistor-fitted air-blast circuit breaker. The test results indicated that arc voltage had a great effect on overvoltage. With the puffer-type SF6 gas circuit breaker, overvoltage was low particularly during short arc times, and high only in the vicinity of the 0.5 cycle corresponding to maximum arc time. A digital calculation of overvoltage waveforms by using nonlinear arc voltage represented by base arc voltage and a normal function revealed that arccontained interruptions could be simulated very well.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.