Abstract

Results of arc reignition voltages during current interruption of frequencies from 5.9 to 60 kHz by a short vacuum gap are presented. Measured arc reignition voltages depend on current amplitude and frequency, the values of preliminary arc current at the moment of switching on the HF current, and the discharge mode in the preceding current semiwave. Threshold amplitudes of the first semiwave of currents l/sub m1l/ and I/sub m1h/ as a function of frequency are determined. I/sub m1l/ and I/sub m1h/ divide current into three ranges to which different kinds of arc reignition voltage distribution correspond. Particularly large dispersion of reignition voltages takes place in the current range from I/sub m1l/ to I/sub m1h/. The threshold current I/sub m1h/ is inversely proportional to frequency in the range from about 10 to 60 kHz, which is in agreement with the elaborated mathematical model.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.