Abstract

The standard impulse voltage calibrator is the key equipment for impulse voltage traceability, and its accuracy directly affects the measurement accuracy of impulse voltage measurement system. International comparison is best important method to ensure the unification of national quantities. In this paper, the developed standard impulse calibrator is compared with the standard digitizer of the Physikalisch-Technische Bundesanstalt (PTB), The standard calibrator can generate three kinds of full-wave of lightning and full-wave of operation with different time parameters. The measurement error of the output voltage of the calibrator measured by PTB's digitizer is less than (+0.1%) and the measurement error of the time parameter is less than (+0.5%). The digitizer of National Center for High Voltage Measurement (NCHVM) is also calibrated by standard calibrator, and the comparison results are evaluated. From the calculation results, it can be seen that the comparison results are satisfactory, and the measurement level evaluation of the digital recorder of the two laboratories are accurate.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.