Abstract

Integrating power plants on long lines and weak power systems requires some care. To this effect, a study was conducted to determine if severe disturbances could result when a hydraulic production plant is integrated along a very long radial transmission line. Frequency responses were evaluated to identify possible resonant system operating conditions. Many events such as faults, transformer energizing and line opening were investigated. All power plant synchronous machines were represented including exciter and governor regulators. Impact of dynamic modeling of the load was examined. The study demonstrates that the overall protective strategy implemented will limit worst overvoltage constraints imposed to equipment and load within an acceptable level.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call