Abstract

The reliability of meshed DC grids mainly relies on their ability in DC fault protection and line power flow managing. Multiple DC circuit breakers (DCCB) and current flow controller (CFC) need to be installed, which significantly increases the system cost. A novel current flow controller integrated with hybrid dc circuit breaker (CFC-IHCB) is proposed to significantly reduce the loss and cost of the whole system. Only one unidirectional IGBT string based main breaker branch is needed for <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">n</i> lines, and the CFC function is integrated into the load communication switches (LCSs). The basic working principle of proposed topology is presented and analyzed. The functionality is verified and a comparison of the proposed solution and other DCCB/CFC solutions is given based on a multi-terminal HVDC system case study.