Abstract

This paper introduces integrated models of distribution transformers and their loads for three-phase power flow analyses. All transformer connections can be easily included, such as single-phase, open wye, open delta and three-phase. For an existing three-phase power flow program without rigorous transformer models, only a slight modification of this program is needed to analyze distribution systems in more detail by using these proposed models. For those with rigorous transformer models, the rigorous transformer models usually make the program converge with difficulty, or even diverge. The convergence characteristics of these program can be dramatically improved if proposed integrated models are used instead of the rigorous transformer models. Moreover, these models can be easily applied by some functions of advanced distribution management systems or automatic mapping and facility management systems, such as transformer load management and feeder load management, to evaluate the individual phase loads along a feeder.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.