Abstract

Important key technologies of a high-temperature superconducting (HTS) transformer may include the HTS wire technology, cooling, AC loss reduction, large current technology, and cryogenic temperature insulation. Among them, the cryogenic temperature insulation technology will be specifically a core technology for ensuring reliability for the smaller size, stability, economic efficiency of a HTS transformer.In this paper, we have simulated a HTS transformer applied with continuous transposed conductor, which has been studied as a way of reducing AC loss. Also, we analyzed the insulation composition and considered various characteristics of insulation breakdown in liquid nitrogen. Insulation design was realized in a way of calculating breakdown voltage of 0.1% with Weibull statistical treatment of the obtained experimental results and calculating insulation distance meeting basic impulse insulation level (BIL) 750kV, a target voltage.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call