Abstract

In this paper focus is given to the insulation co-ordination of a closed system with integrated surge arresters. The calculations of transient overvoltages are made with typical applications of the integration of GIL in the 400 kV net of overhead lines. The overvoltages in the system are calculated and discussed for system lengths of 1 km and 10 km. Recommendations for such applications for the insulation levels are given. The GIL design configuration, the lightning overvoltages of overhead lines, and the overvoltages in the GIL are discussed under respect of overvoltage protection measures. Together with the use of surge arresters the insulation levels due to overvoltages are discussed. The insulation co-ordination is a very important measure for system optimization. Calculated values found for the insulation level of the GIL were proven with type tests and long duration test set-ups. Some test results are also explained in this paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.