Abstract
Safe startup and operation of the nuclear reactor require neutron-sensing instruments to cover a range of about 109. This coverage is obtained by a counting rate meter, a period meter, and a high level power indicator. At normal operating levels, the reactor is regulated by the high level power controller and protected by the high level trips. Emergency shutdown of the reactor can be initiated by any one of 54 different conditions. Since these safety circuits are almost 100% “fail safe”, careful design, good maintenance, and cautious operation have been necessary to avoid accidental shutdowns. The period trips and high level trips are provided in triplicate for safety and are coincidence-connected in pairs to guard against accidental shutdown. The use of suppressed-zero circuits has proved helpful. The theory of coincidence-connected trips is briefly discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Transactions of the Institute of Radio Engineers Professional Group on Nuclear Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.