Abstract
Present Federal regulations which specify maximum instantaneous circuit breaker settings for the short-circuit protection of coal mine trailing cables are discussed. The characteristics of mine power systems that limit short-circuit current in three-phase trailing cables are analyzed and minimum expected short-circuit currents for three-phase 480-, 600-, and 1040-V trailing cables are tabulated. New maximum instantaneous circuit breaker settings, based on minimum expected short-circuit currents and typical breaker tolerances, are proposed with emphasis on safety. Finally, atypical mine power systems are discussed and field tests cited.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.