Abstract

Praxair, Inc. has provided cooling to the HTS cable at the Bixby Road substation in Columbus, Ohio for the past year. The refrigeration has been supplied by an open-loop liquid nitrogen system. Data collected during system operation indicate that the average heat load from the HTS cable is 1.6 kW and the average total heat load on the system is 4.9 kW. In order to more effectively provide HTS cable refrigeration, Praxair has developed a large capacity Stirling-type pulse tube cryocooler. Performance testing of prototype and initial production models of the pulse tube coldhead has demonstrated a refrigeration capacity for nitrogen subcooling of 1 kW at 77 K when a 20 kW, dual-opposed pressure wave generator is used to generate acoustic power for the cryocooler. The initial production models of this pulse tube refrigerator are ready for deployment for field testing at Bixby Road. Operation of these pulse tube units will reduce the nitrogen consumption of the open-loop cooling system and data on the reliability and performance of the cryocoolers will be collected.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.