Abstract

Southwire Company has installed, tested and is operating the first real-world application of a high-temperature superconducting cable system at its headquarters in Carrollton, GA, USA. The cable is powering three Southwire manufacturing plants, marking the first time a company has successfully made the difficult transition front laboratory to practical field application of an HTS cable. The cables are rated at 12.4-kV, 1250-A, 60 Hz and are cooled with pressurized liquid nitrogen at temperatures from 70-80 K. Before placing the cables into service, extensive offline electrical testing was performed including voltage withstand, measurement of DC critical current, extended load current testing, rated voltage testing and partial discharge measurement. The cables were energized on Jan. 5, 2000 for online testing and operation, and by the end of August 2000, had provided 100% of the customer load for 2164 hours.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.