Abstract

Infrared thermography (IRT) has been widely used in detecting the subsurface delamination of bridge deck. However, IRT inspection on delamination zones of the bridge deck which have limited exposure to direct solar radiation (e.g., the bottom surface of the bridge deck) is rather challenging due to the relatively low thermal contrast (∆T) development in these zones. Therefore, the purpose of this study is to conduct a series of experimental studies in conjunction with numerical modeling for investigating the effectiveness of IRT in delamination detection of bridge deck components which are normally not exposed to direct solar radiation. Specially, the effects of different environmental conditions, thickness of bridge deck, and defect characteristics on the absolute thermal contrast (∆T) development were systematically investigated. The results show that IRT can effectively detect the subsurface delamination of concrete bridge deck located in regions that are not exposed to the direct solar radiation. In addition, the development of detectable thermal contrast (>0.5°C) is much dependent on the rate of change in ambient temperature with a suitable detection period between 8 am and 4 pm. Furthermore, it shows that the value of ∆T increases with the increase of bridge deck thickness and delamination size.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.