Abstract

Ethylene–propylene rubber (EPR) cable is the most commonly used type in high-speed railway. Several flashover accidents take place in cable termination in an extremely cold environment. In this study, EPR cable terminations were tested in a simulated low-temperature system with varied applied voltages. The results showed that the differences in elastic modulus and free space volume between EPR insulation and stress control tube (SCT) in a frigid environment would lead to structural defects between them. Damages on the EPR insulation occurred in the form of flashover point when the ambient temperature declined to −30°C and below, with the growth rate of discharge and resulting extent of damage across the EPR/SCT interface being non-linearly related to ambient temperature. Besides, the partial discharge (PD) initial voltage and PD extinction voltage under low-temperature conditions reduced by >40% compared with those at 20°C. The flashover probability of EPR terminations increased significantly, and the shape characteristics of PD patterns have also changed obviously at low temperatures. It can be verified that under the high-voltage and low-temperature conditions, the EPR/SCT interface is prone to organisational mismatch, which will lead to the PD phenomenon and seriously affect the stable operation of EPR cable terminations.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call