Abstract

Break operations of a DC inductive (L=20mH) current from about 1A to about SA at 14V were conducted with Ag and AgSnO <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> contact pairs under different contact opening speeds from 0.5 to 200mm/s in air. Average break arc duration at each current level was calculated under the respective opening speeds. With the small load current levels, the average break arc durations were not influenced by the contact opening speeds, while the arc durations clearly became shorter with increases in the opening speeds at the load currents of 3A or more. However, such tendencies were not significant with the contact opening speeds over 50mm/s even when operated to break a load current of 5A. Those tendencies were observed more clearly with AgSnO <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> contact pairs than with Ag contact pairs. The above results imply that reductions in break arc discharges by increasing contact opening speeds can be realized both with sufficiently large current levels and sufficiently faster opening speed levels.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.