Abstract
This study examines the refrigerant distribution of a dual cold plate system subject to the influence of heating load using a R-134a based vapor compression system with a nominal capacity ranging from 50∼250 W. The cold plate is of identical configuration. Initially, test is performed under an equal heating load for each cold plate (70 W) which then gives rise to a uniform distribution and equal outlet superheat condition. For an unequal heating load, it is found that the distribution of mass flowrate subject to the influence of heating load is strongly related to the outlet states of the two cold plates. For the condition where one of the cold plate is in superheated state while the other is in saturated state, the mass flowrate for the fixed heating load is lower than that of smaller heating load, and the difference increases when the heating load gets smaller due to the influence of accelerational pressure drop. A maximum of 17% difference is seen at a loading ratio of 0.571 (40W/70W). For the condition where both outlet states of cold plate are at superheated states, the mass flowrate for the fixed heating load is marginally higher than that of the smaller heating load, and the difference is insensitive to the rise of heating load. For this situation, the effect of accelerational pressure is negligible, and it is mainly attributed to two-phase/single-phase distribution pertaining to the effect of heating load.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.