Experimental measurements in a spray cooling test rig were carried out for two different heater surface roughnesses and for two different types of nozzles with the dielectric refrigerant R134a. In this paper, results of the heat transfer measurements are presented. The analysis of the results explains the influence of the volumetric flow rate, the surface roughness and the type of nozzle (through the spray parameters) on the spray cooling boiling curve, on the Nusselt number and on the efficiency. It has been found that the effect of a smooth roughness is to delay the onset of the nucleate boiling, but once this regime has started, boiling is so fast that the CHF (Critical Heat Flux) is reached at lower heater temperatures and lower heat fluxes. In a companion paper the sprayed refrigerant film thickness measurements and its relation with the heat transfer measurements are presented.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.