Abstract

For high voltage impulse testing, a standard lightning impulse is defined in IEEE Std. 4 and IEC 60060-1 as a double exponential waveform having a front time T1 = 1.2 μs ± 30% and time to half-value T2 = 50 μs ± 20%. It has been noticed that for a given specimen, it is possible to successfully pass a flashover test at one end of the T1 tolerance range while failing the same test at the opposite end of the tolerance spectrum. Consequently, a systematic approach was adopted to investigate this observation. Up-and-down tests were performed to define the disruptive discharge voltage (critical flashover voltage CFO, U50) for 1, 5, 10, and 15 unit glass insulator strings standard lightning impulses using the minimum acceptance front time value (T1 ≈ 0.84 μs). Tests were repeated using the maximum tolerance value (T1 ≈ 1.56 μs) to investigate the degree of divergence in the flashover value. Particular attention is given to the steepness (voltage-time characteristics) of the applied impulse to consider if tolerance criteria amendment is merited in a future standard revision. As the steepness impact is more renowned in non-uniform geometries, field homogeneity as a function of string length is also incorporated into the analysis.

Highlights

  • Standardization of high voltage test techniques is aimed at promoting the fulfilment of testing requirements

  • For longer insulator strings where field distribution is more asymmetric (10 and 15 unit strings), the highest U50 values were obtained with a short T1 and positive polarity

  • Positive impulses produce significantly lower flashover values compared to negative polarity impulses [5, 9]

Read more

Summary

Introduction

Standardization of high voltage test techniques is aimed at promoting the fulfilment of testing requirements. Insulator strings consisting of 1, 5, 10, and 15 units were tested with both extremes of the front time range (T1 ≈ 0.84 μs and T1 ≈ 0.1.56 μs) while maintaining a relatively constant T2. The test voltage interval ΔV remained within the acceptable range, varying between 1.3...2.8% of U50 depending on the insulator string length (and flashover voltage).

Results
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.