Abstract

Low voltage and single-phase excitation are often used to measure leakage reactance or short-circuit impedance of transformers. Winding distortion may be detected by comparing field results with factory nameplate values measured at 25-100% of the rated current using three-phase excitation. The results of single- and three-phase excitation will not always correlate. If the voltage applied in the field is not properly selected then the data may be influenced by the magnetizing reactance. The resulting difference between the nameplate value and the field data might then lead to erroneous analysis of test results and could be interpreted as an indication of winding distortion. The intent of this paper is to analyze the physics of the process and gain insight on test circuit selection and analysis of the results. Methods for avoiding erroneous test results are suggested.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.