Abstract
Abstract Legionella pneumophila is an environmental pathogen of engineered water systems that can cause different forms of legionellosis - from mild fever to potentially lethal pneumonia. Low concentrations of legionellae in natural habitats can increase markedly in engineered hot water systems where water temperatures are below 55 °C. In the current study, we aimed to investigate the influence of sampling season, hot water temperature and sampling protocol on occurrence of L. pneumophila. A total of 120 hot water samples from 20 apartment buildings were collected in two sampling periods - winter 2014 (n = 60) and summer 2015 (n = 60). Significantly higher occurrence of L. pneumophila was observed in summer 2015. Significant differences in temperature for negative and positive samples were not observed, which can be explained by low water temperatures at the point of water consumption. Temperature above 55 °C was observed only once, for all other sampling events it ranged from 14 °C to 53 °C.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Proceedings of the Latvian Academy of Sciences. Section B. Natural, Exact, and Applied Sciences.
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.