Abstract

To make clear the influence of algae growth at the surface of a polymer insulator in a practical transmission line, the characteristics of ac corona discharge from an aggregate algae particle were investigated. The aggregate algae particle was made of Protococcus viridis. Corona onset voltage from an aggregate algae particle was decreased as relative humidity increased. Under the condition of relatively higher relative humidity, luminous channel of corona discharge became more strongly and the number of corona pulses in the current waveform was increased. For an aggregate algae particle contaminated with sea salt including MgCl2, corona onset voltage decreased drastically at relative humidity above 40%. This property would result from deliquescence of MgCl2. Corona discharge was strongly affected by existence of MgCl2 in an aggregate algae particle. Surface resistance of algae attached to the surface of the silicone rubber sheet decreased in fourth figures for relative humidity from 20 to 90%. Therefore, the existence of algae on the polymer insulator inevitably affects the electric property and the surface property of the polymer insulator.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.