Vibration measurements were performed on two adjacent, three-storey reinforced concrete frame buildings with hollow clay brick infill panels. The first building was a bare frame and the second one was a similar frame infilled with brick panels. The fundamental period for the infilled frame building was much smaller than that of the bare frame building. Using shear beam lumped mass models and the vibration data the actual lateral stiffness of both buildings was identified. The lateral stiffness of the infilled frame building was found to be seven times that of the bare frame building. Four numerical models of the infilled frame building were constructed. The frame and floors were represented using an experimentally validated model and the infill panels by one of three commonly used ‘equivalent diagonal truss’ models or by plane stress finite elements. Only the plane stress finite element model produced a reasonable agreement with the experimental results. Copyright © 1999 John Wiley & Sons, Ltd.